Line 25: Line 25:
  Case Number    : C1-121405343
  Case Number    : C1-121405343
  Internal Order : 1-121712992
  Internal Order : 1-121712992
Solution      : APC will ship new battery


November 22, 2006
November 22, 2006

Revision as of 14:42, 29 January 2007

( Placed on the Right )

Type/Name     : Symmetra RM
Model Number  : SYHF6KT
Serial Number : ED0321000735


Event Log of System Events :

11/20/2006 12:31:22 UPS: Battery failure.
11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.
11/20/2006 12:31:23 UPS: Batteries need immediate replacement.
11/20/2006 12:31:29 UPS: Bad battery condition cleared.
11/20/2006 12:31:42 UPS: Battery failure cleared.
11/20/2006 12:32:18 UPS: Battery failure.
11/20/2006 12:32:19 UPS: Batteries need immediate replacement.
11/20/2006 12:32:34 UPS: Bad battery condition cleared.
11/20/2006 12:32:39 UPS: Battery failure cleared.
11/20/2006 12:32:51 UPS: Number of batteries decreased.
11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.

November 20, 2006

Problem : Bad battery
Model   # SYBT2
Called to APC  : 9-1-800-800-4272  then 4  then 3
Operator       : David and Pole
Case Number    : C1-121405343
Internal Order : 1-121712992
Solution       : APC will ship new battery

November 22, 2006

New battery arrived and installed

Event Log of System Events :

11/22/2006 12:25:25 UPS: Number of batteries increased.
...
12/04/2006 20:45:00 UPS: Passed internal self-test.
...
01/16/2007 16:02:24 UPS: Battery failure.
01/16/2007 16:02:25 UPS: Batteries need immediate replacement.
01/16/2007 16:02:34 UPS: Passed internal self-test.
01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.
01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.
01/18/2007 11:32:25 UPS: Number of batteries decreased.
01/18/2007 11:34:32 UPS: Number of batteries increased.
01/18/2007 11:35:01 UPS: Battery failure cleared.
01/18/2007 11:35:01 UPS: Number of batteries decreased.
01/18/2007 11:35:01 UPS: Bad battery condition cleared.
01/18/2007 11:35:01 UPS: Number of batteries decreased.
01/18/2007 11:35:01 UPS: Bad battery condition cleared.

January 18, 2007

Problem : Bad battery R2 (Second right from top) in Main Frame
Model   # SYBT2
Serial  # ED0328001135
Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).
Operator      : Greg
Case Number   : 1-179095349

January 22, 2007

Note   : New battery arrived and installed as R2 in Main Frame
Model  # SYBT2
Serial # QD0626150474
SO     # 610051437
Tested : Fri, Jun 30, 2006 00:18:28

Event Log of System Events :

01/22/2007 15:03:18 UPS: Number of batteries increased.
01/22/2007 15:05:53 UPS: Passed internal self-test.