Line 29: | Line 29: | ||
Case Number : 1-179095349 | Case Number : 1-179095349 | ||
January 22, 2007 | |||
Note : New battery arrived and installed as R2 in Main Frame | |||
Model # SYBT2 | |||
Serial # QD0626150474 | |||
SO # 610051437 | |||
Tested : Fri, Jun 30, 2006 00:18:28 | |||
Event Log of System Events : | Event Log of System Events : |
Revision as of 12:39, 26 January 2007
( Placed on the Right )
Type/Name : Symmetra RM Model Number : SYHF6KT Serial Number : ED0321000735
Event Log of System Events :
12/04/2006 20:45:00 UPS: Passed internal self-test. 01/16/2007 16:02:24 UPS: Battery failure. 01/16/2007 16:02:25 UPS: Batteries need immediate replacement. 01/16/2007 16:02:34 UPS: Passed internal self-test. 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test. 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test. 01/18/2007 11:32:25 UPS: Number of batteries decreased. 01/18/2007 11:34:32 UPS: Number of batteries increased. 01/18/2007 11:35:01 UPS: Battery failure cleared. 01/18/2007 11:35:01 UPS: Number of batteries decreased. 01/18/2007 11:35:01 UPS: Bad battery condition cleared. 01/18/2007 11:35:01 UPS: Number of batteries decreased. 01/18/2007 11:35:01 UPS: Bad battery condition cleared.
January 18, 2007
Problem : Bad battery R2 (Second right from top) in Main Frame Model # SYBT2 Serial # ED0328001135 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra). Operator : Greg Case Number : 1-179095349
January 22, 2007
Note : New battery arrived and installed as R2 in Main Frame Model # SYBT2 Serial # QD0626150474 SO # 610051437 Tested : Fri, Jun 30, 2006 00:18:28
Event Log of System Events :
01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171. 01/22/2007 15:03:18 UPS: Number of batteries increased. 01/22/2007 15:05:53 UPS: Passed internal self-test.