UPS (Uninterruptible Power Supplies): Difference between revisions
No edit summary |
No edit summary |
||
Line 21: | Line 21: | ||
[http://clonweb/wiki/clondocs/Downloads/pcns221win.exe WindowsXP]. Mac OS X version 10.2 is also supported as 'PowerChute Network Shutdown v2.0.0', part number SFPCNS200, file date 01/27/2003: [http://clonweb/wiki/clondocs/Downloads/ASTE-6Z5QDK_R1_EN.pdf Installation Guide], [http://clonweb/wiki/clondocs/Downloads/pcns200.tar MacOSX]. | [http://clonweb/wiki/clondocs/Downloads/pcns221win.exe WindowsXP]. Mac OS X version 10.2 is also supported as 'PowerChute Network Shutdown v2.0.0', part number SFPCNS200, file date 01/27/2003: [http://clonweb/wiki/clondocs/Downloads/ASTE-6Z5QDK_R1_EN.pdf Installation Guide], [http://clonweb/wiki/clondocs/Downloads/pcns200.tar MacOSX]. | ||
Shortly, goto ''/usr/local/downloads'' directory; on Solaris(Sparc) run ''./pcns221sol.bin'', on Linux run ''./pcns221lnx.bin''; on Solaris(x86) goto ''/usr/local/downloads/PowerChute'' and run command ''java -cp .:install.jar:util.jar load''. Follow instructions, choose ''/opt/PowerChute'' as installation directory, ''Typical Install'', and UPS_CHB1's IP address as ''Management Card IP'' (we assume that UPS_CHB1 have bigger load then other UPSes). | Shortly, goto ''/usr/local/downloads'' directory; on Solaris(Sparc) run ''./pcns221sol.bin'', on Linux run ''./pcns221lnx.bin''; on Solaris(x86) goto ''/usr/local/downloads/PowerChute'' and run command ''java -cp .:install.jar:util.jar load''. Follow instructions, choose ''/opt/PowerChute'' as installation directory, ''Typical Install'', and UPS_CHB1's IP address as ''Management Card IP'' (we assume that UPS_CHB1 have bigger load then other UPSes). All other settings are default. |
Revision as of 21:02, 28 September 2007
CLON cluster equipped with two big SYMMETRA RM 6000 Single-phase UPSes from APC Corporation. These UPSes are multi-battery systems. In case of something wrong with UPSes follow the instruction of UPS Troubleshooting.
Smaller UPSes ...
All UPSes are connected to emergency generator.
All connections (ether via Web interface or SSH) allowed only from local subnet.
web link to http://UPS_CHB1/ (device/apc)
web link to http://UPS_CHB2/ (device/apc)
SYMMETRA RM 6000 firmware upgrade
Enable SYMMETRA FTP service using its web interface. Download appropriate firmware from http://www.apc.com/ web site. Search not for SYMMETRA but for 'UPS Network Management Cards'. Last time apc_hw02_aos334_sy331.exe was used, it was listed as 'Network Management Card v3.3.1 Firmware Executable for Symmetra Single-Phase UPS with AP9617/8/9', part number SFSY331, file date 01/23/2007. To install, place it into CUE home directory, run metaframe and click on firmware file. Several files will be installed, upgrade program will be started and text GUI will shows up. Type SYMMETRA IP and admin username/password, start firmware installation and wait several minutes for completion. Repeat for all SYMMETRA devices (currently we have 2 of them). Remove all installed files from CUE home directory.
PowerChute Network Shutdown
That free software is used to shut down computers when UPS is running out of charge. Can be downloaded from http://www.apc.com/, 27-sep-2007 following files were downloaded for 'PowerChute Network Shutdown v2.2.1', part number SFPCNS221, file date 11/15/2006: Installation Guide, Linux, Solaris(Sparc), Solaris(x86), WindowsXP. Mac OS X version 10.2 is also supported as 'PowerChute Network Shutdown v2.0.0', part number SFPCNS200, file date 01/27/2003: Installation Guide, MacOSX.
Shortly, goto /usr/local/downloads directory; on Solaris(Sparc) run ./pcns221sol.bin, on Linux run ./pcns221lnx.bin; on Solaris(x86) goto /usr/local/downloads/PowerChute and run command java -cp .:install.jar:util.jar load. Follow instructions, choose /opt/PowerChute as installation directory, Typical Install, and UPS_CHB1's IP address as Management Card IP (we assume that UPS_CHB1 have bigger load then other UPSes). All other settings are default.