<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://clonwiki0.jlab.org/wiki/api.php?action=feedcontributions&amp;feedformat=atom&amp;user=Sergpozd</id>
	<title>CLONWiki - User contributions [en]</title>
	<link rel="self" type="application/atom+xml" href="https://clonwiki0.jlab.org/wiki/api.php?action=feedcontributions&amp;feedformat=atom&amp;user=Sergpozd"/>
	<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=Special:Contributions/Sergpozd"/>
	<updated>2026-05-07T09:27:40Z</updated>
	<subtitle>User contributions</subtitle>
	<generator>MediaWiki 1.42.1</generator>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3077</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3077"/>
		<updated>2007-12-10T15:17:20Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Electronics repair */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* Trace current repair&lt;br /&gt;
&lt;br /&gt;
 - Motorola PMC Card&lt;br /&gt;
 - two HV Mainframes&lt;br /&gt;
 - ORTEC HV Card&lt;br /&gt;
&lt;br /&gt;
* Send out, &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; all should be prepared for Monday December 10, 2007 !!! &amp;lt;/span&amp;gt;&lt;br /&gt;
&lt;br /&gt;
 - get quotation for LeCroy 2313&lt;br /&gt;
 - get quotation for LeCroy HV Card 1461N&lt;br /&gt;
 - make a requisition based on quotations&lt;br /&gt;
 - quotation obtained for 5 Discriminators and 5 HV Cards&lt;br /&gt;
 - pack 5 LeCroy 2313 Discriminator &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; &lt;br /&gt;
 - double check one 1461P !!!!!&lt;br /&gt;
 - collect 5 !!!  1461N and pack them &amp;lt;/span&amp;gt; &lt;br /&gt;
 - boxing and shipping out for repair&lt;br /&gt;
&lt;br /&gt;
* Test repaired electronics&lt;br /&gt;
&lt;br /&gt;
 - three LeCroy HV Mainframe 1458:&lt;br /&gt;
   * currently all in test in CR, 6-Dec-2007&lt;br /&gt;
   * Mainframe-1 (ARCnet=1) has one HV Card in slot#2, all ch. loaded&lt;br /&gt;
   * Mainframe-3 (ARCnet=3) has one HV Card in slot#4, all ch. empty&lt;br /&gt;
   * Mainframe-2 (ARCnet=2) has 10 HV Cards, all loaded except sl.#11&lt;br /&gt;
&lt;br /&gt;
 - three CAEN Discriminator v895:&lt;br /&gt;
   a) one in CR testsetup;&lt;br /&gt;
   b) two in Benjamin Raydo testsetup.&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3076</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3076"/>
		<updated>2007-12-07T21:47:34Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Electronics repair */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* Trace current repair&lt;br /&gt;
&lt;br /&gt;
 - Motorola PMC Card&lt;br /&gt;
 - two HV Mainframes&lt;br /&gt;
 - ORTEC HV Card&lt;br /&gt;
&lt;br /&gt;
* Send out, &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; all should be prepared for Monday December 9, 2007 !!! &amp;lt;/span&amp;gt;&lt;br /&gt;
&lt;br /&gt;
 - get quotation for LeCroy 2313&lt;br /&gt;
 - get quotation for LeCroy HV Card 1461N&lt;br /&gt;
 - make a requisition based on quotations&lt;br /&gt;
 - quotation obtained for 5 Discriminators and 5 HV Cards&lt;br /&gt;
 - pack 5 LeCroy 2313 Discriminator &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; &lt;br /&gt;
 - double check one 1461P !!!!!&lt;br /&gt;
 - collect 5 !!!  1461N and pack them &amp;lt;/span&amp;gt; &lt;br /&gt;
 - boxing and shipping out for repair&lt;br /&gt;
&lt;br /&gt;
* Test repaired electronics&lt;br /&gt;
&lt;br /&gt;
 - three LeCroy HV Mainframe 1458:&lt;br /&gt;
   * currently all in test in CR, 6-Dec-2007&lt;br /&gt;
   * Mainframe-1 (ARCnet=1) has one HV Card in slot#2, all ch. loaded&lt;br /&gt;
   * Mainframe-3 (ARCnet=3) has one HV Card in slot#4, all ch. empty&lt;br /&gt;
   * Mainframe-2 (ARCnet=2) has 10 HV Cards, all loaded except sl.#11&lt;br /&gt;
&lt;br /&gt;
 - three CAEN Discriminator v895:&lt;br /&gt;
   a) one in CR testsetup;&lt;br /&gt;
   b) two in Benjamin Raydo testsetup.&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3075</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3075"/>
		<updated>2007-12-07T21:46:11Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Electronics repair */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* Trace current repair&lt;br /&gt;
&lt;br /&gt;
 - Motorola PMC Card&lt;br /&gt;
 - two HV Mainframes&lt;br /&gt;
 - ORTEC HV Card&lt;br /&gt;
&lt;br /&gt;
* Send out, &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; all should be prepared for Monday December 9, 2007 !!! &amp;lt;/span&amp;gt;&lt;br /&gt;
&lt;br /&gt;
 - get quotation for LeCroy 2313&lt;br /&gt;
 - get quotation for LeCroy HV Card 1461N&lt;br /&gt;
 - make a requisition based on quotations&lt;br /&gt;
 - quotation obtained for 5 Discriminators and 5 HV Cards&lt;br /&gt;
 - pack 5 LeCroy 2313 Discriminator&lt;br /&gt;
 - double check one 1461P &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; ! ! ! &amp;lt;/span&amp;gt;&lt;br /&gt;
 - collect 5 &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; ! ! ! &amp;lt;/span&amp;gt; 1461N and pack them&lt;br /&gt;
 - boxing and shipping out for repair&lt;br /&gt;
&lt;br /&gt;
* Test repaired electronics&lt;br /&gt;
&lt;br /&gt;
 - three LeCroy HV Mainframe 1458:&lt;br /&gt;
   * currently all in test in CR, 6-Dec-2007&lt;br /&gt;
   * Mainframe-1 (ARCnet=1) has one HV Card in slot#2, all ch. loaded&lt;br /&gt;
   * Mainframe-3 (ARCnet=3) has one HV Card in slot#4, all ch. empty&lt;br /&gt;
   * Mainframe-2 (ARCnet=2) has 10 HV Cards, all loaded except sl.#11&lt;br /&gt;
&lt;br /&gt;
 - three CAEN Discriminator v895:&lt;br /&gt;
   a) one in CR testsetup;&lt;br /&gt;
   b) two in Benjamin Raydo testsetup.&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3074</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3074"/>
		<updated>2007-12-07T21:39:56Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Electronics repair */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* Trace current repair&lt;br /&gt;
&lt;br /&gt;
 - Motorola PMC Card&lt;br /&gt;
 - two HV Mainframes&lt;br /&gt;
 - ORTEC HV Card&lt;br /&gt;
&lt;br /&gt;
* Send out, &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; all should be prepared for Monday December 9, 2007 !!! &amp;lt;/span&amp;gt;&lt;br /&gt;
&lt;br /&gt;
 - get quotation for LeCroy 2313&lt;br /&gt;
 - get quotation for LeCroy HV Card 1461N&lt;br /&gt;
 - make a requisition based on quotations&lt;br /&gt;
 - boxing and shipping out for repair&lt;br /&gt;
&lt;br /&gt;
* Test repaired electronics&lt;br /&gt;
&lt;br /&gt;
 - three LeCroy HV Mainframe 1458:&lt;br /&gt;
   * currently all in test in CR, 6-Dec-2007&lt;br /&gt;
   * Mainframe-1 (ARCnet=1) has one HV Card in slot#2, all ch. loaded&lt;br /&gt;
   * Mainframe-3 (ARCnet=3) has one HV Card in slot#4, all ch. empty&lt;br /&gt;
   * Mainframe-2 (ARCnet=2) has 10 HV Cards, all loaded except sl.#11&lt;br /&gt;
&lt;br /&gt;
 - three CAEN Discriminator v895:&lt;br /&gt;
   a) one in CR testsetup;&lt;br /&gt;
   b) two in Benjamin Raydo testsetup.&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3073</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3073"/>
		<updated>2007-12-07T21:38:08Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Electronics repair */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* Trace current repair&lt;br /&gt;
&lt;br /&gt;
 - Motorola PMC Card&lt;br /&gt;
 - two HV Mainframes&lt;br /&gt;
 - ORTEC HV Card&lt;br /&gt;
&lt;br /&gt;
* Send out, &amp;lt;span style=&amp;quot;color:red&amp;quot;&amp;gt; all should be prepared for Monday December 9, 2007 !!!&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
 - get quotation for LeCroy 2313&lt;br /&gt;
 - get quotation for LeCroy HV Card 1461N&lt;br /&gt;
 - make a requisition based on quotations&lt;br /&gt;
 - boxing and shipping out for repair&lt;br /&gt;
&lt;br /&gt;
* Test repaired electronics&lt;br /&gt;
&lt;br /&gt;
 - three LeCroy HV Mainframe 1458:&lt;br /&gt;
   * currently all in test in CR, 6-Dec-2007&lt;br /&gt;
   * Mainframe-1 (ARCnet=1) has one HV Card in slot#2, all ch. loaded&lt;br /&gt;
   * Mainframe-3 (ARCnet=3) has one HV Card in slot#4, all ch. empty&lt;br /&gt;
   * Mainframe-2 (ARCnet=2) has 10 HV Cards, all loaded except sl.#11&lt;br /&gt;
&lt;br /&gt;
 - three CAEN Discriminator v895:&lt;br /&gt;
   a) one in CR testsetup;&lt;br /&gt;
   b) two in Benjamin Raydo testsetup.&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3072</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3072"/>
		<updated>2007-12-06T19:44:18Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Electronics repair */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* Trace current repair&lt;br /&gt;
&lt;br /&gt;
 - Motorola PMC Card&lt;br /&gt;
 - two HV Mainframes&lt;br /&gt;
 - ORTEC HV Card&lt;br /&gt;
&lt;br /&gt;
* Send out&lt;br /&gt;
&lt;br /&gt;
 - get quotation for LeCroy 2313&lt;br /&gt;
 - get quotation for LeCroy HV Card 1461N&lt;br /&gt;
 - make a requisition based on quotations&lt;br /&gt;
 - boxing and shipping out for repair&lt;br /&gt;
&lt;br /&gt;
* Test repaired electronics&lt;br /&gt;
&lt;br /&gt;
 - three LeCroy HV Mainframe 1458:&lt;br /&gt;
   * currently all in test in CR, 6-Dec-2007&lt;br /&gt;
   * Mainframe-1 (ARCnet=1) has one HV Card in slot#2, all ch. loaded&lt;br /&gt;
   * Mainframe-3 (ARCnet=3) has one HV Card in slot#4, all ch. empty&lt;br /&gt;
   * Mainframe-2 (ARCnet=2) has 10 HV Cards, all loaded except sl.#11&lt;br /&gt;
&lt;br /&gt;
 - three CAEN Discriminator v895:&lt;br /&gt;
   a) one in CR testsetup;&lt;br /&gt;
   b) two in Benjamin Raydo testsetup.&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3071</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3071"/>
		<updated>2007-12-06T19:21:14Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Electronics repair ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* trace current repair&lt;br /&gt;
&lt;br /&gt;
 * rrr&lt;br /&gt;
&lt;br /&gt;
 * ddd&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* test repaired electronics&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3070</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3070"/>
		<updated>2007-12-06T19:16:06Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&lt;br /&gt;
== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
== Test repaired electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== CAMAC electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* check board availability&lt;br /&gt;
&lt;br /&gt;
* check alive status&lt;br /&gt;
&lt;br /&gt;
* arrange and revise test-scripts&lt;br /&gt;
&lt;br /&gt;
* revise photon trigger logic&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3069</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3069"/>
		<updated>2007-12-05T22:18:46Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* File repair documentations */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&lt;br /&gt;
&lt;br /&gt;
== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* sort by functionality&lt;br /&gt;
&lt;br /&gt;
* sort by repair company&lt;br /&gt;
&lt;br /&gt;
* trace by RMA&lt;br /&gt;
&lt;br /&gt;
* account of repair frequency and quality&lt;br /&gt;
&lt;br /&gt;
== Test repaired electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3068</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3068"/>
		<updated>2007-12-05T22:13:51Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* Inventory DB for Hall B electronics */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&lt;br /&gt;
&lt;br /&gt;
== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
* complete inventory list of Hall B electronics&lt;br /&gt;
&lt;br /&gt;
* modify this list in easy-view/easy-search format&lt;br /&gt;
&lt;br /&gt;
* label all coming-in and coming-out electronics&lt;br /&gt;
&lt;br /&gt;
* excess unused and ancient electronics&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Test repaired electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3067</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3067"/>
		<updated>2007-12-05T22:02:55Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&lt;br /&gt;
&lt;br /&gt;
== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Test repaired electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Maintenance of Hall B electronics ==&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3066</id>
		<title>TO DO List for SP</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=TO_DO_List_for_SP&amp;diff=3066"/>
		<updated>2007-12-05T22:01:56Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Inventory DB for Hall B electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== File repair documentations ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Test repaired electronics ==&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
== Maintenance of current Hall B electronics ==&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=Main_Page&amp;diff=3065</id>
		<title>Main Page</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=Main_Page&amp;diff=3065"/>
		<updated>2007-12-05T21:48:51Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: /* CLAS Online Group At Work */&lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&amp;lt;big&amp;gt;&#039;&#039;&#039;MediaWiki has been successfully installed.&#039;&#039;&#039;&amp;lt;/big&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Consult the [http://meta.wikipedia.org/wiki/MediaWiki_User%27s_Guide User&#039;s Guide] for information on using the wiki software.&lt;br /&gt;
&lt;br /&gt;
== Getting started ==&lt;br /&gt;
&lt;br /&gt;
* [http://www.mediawiki.org/wiki/Help:Configuration_settings Configuration settings list]&lt;br /&gt;
* [http://www.mediawiki.org/wiki/Help:FAQ MediaWiki FAQ]&lt;br /&gt;
* [http://mail.wikipedia.org/mailman/listinfo/mediawiki-announce MediaWiki release mailing list]&lt;br /&gt;
&lt;br /&gt;
== CLAS Online Group At Work ==&lt;br /&gt;
&lt;br /&gt;
[[Scratch]]&lt;br /&gt;
&lt;br /&gt;
[[ERROR Book]] - DAQ and Online errors observed&lt;br /&gt;
&lt;br /&gt;
[[TO DO Lists]]&lt;br /&gt;
&lt;br /&gt;
[[TO DO List for Nerses]]&lt;br /&gt;
&lt;br /&gt;
[[TO DO List for SP]]&lt;br /&gt;
&lt;br /&gt;
[[Run Information]]&lt;br /&gt;
&lt;br /&gt;
[[CLON Group Meetings]]&lt;br /&gt;
&lt;br /&gt;
[[CLAS DAQ Upgrade]]&lt;br /&gt;
&lt;br /&gt;
[[Flash ADC Studies]]&lt;br /&gt;
&lt;br /&gt;
[[DVCS Trigger System]] (in progress)&lt;br /&gt;
&lt;br /&gt;
[[CLAS12 Trigger System Design]] (in progress)&lt;br /&gt;
&lt;br /&gt;
== CLAS Online System Documentation ==&lt;br /&gt;
&lt;br /&gt;
[[CLON Cluster System Administration]]&lt;br /&gt;
&lt;br /&gt;
[[CLAS Online Software]]&lt;br /&gt;
&lt;br /&gt;
[[CLAS Online Hardware]]&lt;br /&gt;
&lt;br /&gt;
== CLAS Online System Index ==&lt;br /&gt;
&lt;br /&gt;
[[CLON Index]]&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2603</id>
		<title>JLAB Discriminators</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2603"/>
		<updated>2007-10-11T17:24:51Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;First version was developed by James Proffitt and is used in tagger system. It was tested by Sergey Pozdnyakov. Results of tests are presented on the next few slides:&lt;br /&gt;
&lt;br /&gt;
* Width distribution ( [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.eps eps] [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Threshold distribution ( [http://clonweb/wiki/clondocs/Docs/JLabDiscr_thresh_vs_dac.eps eps] [http://clonweb/wiki/clondocs/Docs/JLabDiscr_thresh_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for JLab Discr. ( [http://clonweb/wiki/clondocs/Docs/Res_JLabDiscr_Leading_Edge.pdf pdf] [http://clonweb/wiki/clondocs/Docs/Res_JLabDiscr_Leading_Edge.eps eps])&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for LeCroy 2313 Discr. (for compare) ( [http://clonweb/wiki/clondocs/Docs/Res_2313_Leading_Edge.pdf pdf] [http://clonweb/wiki/clondocs/Docs/Res_2313_Leading_Edge.eps eps])&lt;br /&gt;
&lt;br /&gt;
* Resolution of Trailing Edge for JLab Discr. ( [http://clonweb/wiki/clondocs/Docs/Res_JLabDiscr_Trailing_Edge.pdf pdf] [http://clonweb/wiki/clondocs/Docs/Res_JLabDiscr_Trailing_Edge.eps eps])&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Following changes were recommended to make that board suitable for CLAS12:&lt;br /&gt;
&lt;br /&gt;
* remove preamplifier&lt;br /&gt;
&lt;br /&gt;
* add test input&lt;br /&gt;
&lt;br /&gt;
* add second output connector&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
As on October 11, 2007 the possibility of board redesign was discussed with Volker, Chris and Stan Majewski, and we are waiting for Stan&#039;s final word.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2602</id>
		<title>JLAB Discriminators</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2602"/>
		<updated>2007-10-11T17:21:32Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;First version was developed by James Proffitt and is used in tagger system. It was tested by Sergey Pozdnyakov. Results of tests are presented on the next few slides:&lt;br /&gt;
&lt;br /&gt;
* Width distribution ( [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.eps eps] [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Threshold distribution ( [http://clonweb/wiki/clondocs/Docs/JLabDiscr_thresh_vs_dac.eps eps] [http://clonweb/wiki/clondocs/Docs/JLabDiscr_thresh_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for LeCroy 2313 Discr. (for compare)&lt;br /&gt;
&lt;br /&gt;
* Resolution of Trailing Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Following changes were recommended to make that board suitable for CLAS12:&lt;br /&gt;
&lt;br /&gt;
* remove preamplifier&lt;br /&gt;
&lt;br /&gt;
* add test input&lt;br /&gt;
&lt;br /&gt;
* add second output connector&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
As on October 11, 2007 the possibility of board redesign was discussed with Volker, Chris and Stan Majewski, and we are waiting for Stan&#039;s final word.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2601</id>
		<title>JLAB Discriminators</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2601"/>
		<updated>2007-10-11T17:20:01Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;First version was developed by James Proffitt and is used in tagger system. It was tested by Sergey Pozdnyakov. Results of tests are presented on the next few slides:&lt;br /&gt;
&lt;br /&gt;
* Width distribution (    [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.eps eps],   [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Threshold distribution&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for LeCroy 2313 Discr. (for compare)&lt;br /&gt;
&lt;br /&gt;
* Resolution of Trailing Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Following changes were recommended to make that board suitable for CLAS12:&lt;br /&gt;
&lt;br /&gt;
* remove preamplifier&lt;br /&gt;
&lt;br /&gt;
* add test input&lt;br /&gt;
&lt;br /&gt;
* add second output connector&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
As on October 11, 2007 the possibility of board redesign was discussed with Volker, Chris and Stan Majewski, and we are waiting for Stan&#039;s final word.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2600</id>
		<title>JLAB Discriminators</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2600"/>
		<updated>2007-10-11T17:19:33Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;First version was developed by James Proffitt and is used in tagger system. It was tested by Sergey Pozdnyakov. Results of tests are presented on the next few slides:&lt;br /&gt;
&lt;br /&gt;
* Width distribution (  [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.eps eps], [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Threshold distribution&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for LeCroy 2313 Discr. (for compare)&lt;br /&gt;
&lt;br /&gt;
* Resolution of Trailing Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Following changes were recommended to make that board suitable for CLAS12:&lt;br /&gt;
&lt;br /&gt;
* remove preamplifier&lt;br /&gt;
&lt;br /&gt;
* add test input&lt;br /&gt;
&lt;br /&gt;
* add second output connector&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
As on October 11, 2007 the possibility of board redesign was discussed with Volker, Chris and Stan Majewski, and we are waiting for Stan&#039;s final word.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2599</id>
		<title>JLAB Discriminators</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2599"/>
		<updated>2007-10-11T17:18:40Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;First version was developed by James Proffitt and is used in tagger system. It was tested by Sergey Pozdnyakov. Results of tests are presented on the next few slides:&lt;br /&gt;
&lt;br /&gt;
* Width distribution ([http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.eps eps], [http://clonweb/wiki/clondocs/Docs/JLabDiscr_width_vs_dac.pdf pdf])&lt;br /&gt;
&lt;br /&gt;
* Threshold distribution&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for LeCroy 2313 Discr. (for compare)&lt;br /&gt;
&lt;br /&gt;
* Resolution of Trailing Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Following changes were recommended to make that board suitable for CLAS12:&lt;br /&gt;
&lt;br /&gt;
* remove preamplifier&lt;br /&gt;
&lt;br /&gt;
* add test input&lt;br /&gt;
&lt;br /&gt;
* add second output connector&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
As on October 11, 2007 the possibility of board redesign was discussed with Volker, Chris and Stan Majewski, and we are waiting for Stan&#039;s final word.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2583</id>
		<title>JLAB Discriminators</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=JLAB_Discriminators&amp;diff=2583"/>
		<updated>2007-10-11T15:55:36Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;First version was developed by James Proffitt and is used in tagger system. It was tested by Sergey Pozdnyakov. Results of tests are presented on the next few slides:&lt;br /&gt;
&lt;br /&gt;
* Width distribution&lt;br /&gt;
&lt;br /&gt;
* Threshold distribution&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
* Resolution of Leading Edge for LeCroy 2313 Discr. (for compare)&lt;br /&gt;
&lt;br /&gt;
* Resolution of Trailing Edge for JLab Discr.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Following changes were recommended to make that board suitable for CLAS12:&lt;br /&gt;
&lt;br /&gt;
* remove preamplifier&lt;br /&gt;
&lt;br /&gt;
* add test input&lt;br /&gt;
&lt;br /&gt;
* add second output connector&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
As on October 11, 2007 the possibility of board redesign was discussed with Volker, Chris and Stan Majewski, and we are waiting for Stan&#039;s final word.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=EPICS:_generation_of_DBs_and_GUIs_for_HV&amp;diff=1885</id>
		<title>EPICS: generation of DBs and GUIs for HV</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=EPICS:_generation_of_DBs_and_GUIs_for_HV&amp;diff=1885"/>
		<updated>2007-04-05T14:21:25Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt; NOTE: normally all environment variables are set, with one exception: &#039;&#039;cc_mf&#039;&#039; (counting house classc0) is using old EPICS;&lt;br /&gt;
 if you want to    work with &#039;&#039;cc_mf&#039;&#039; execute $CLAS/epicsBold/.setup script; it will redefine environment; proceed as described below.&lt;br /&gt;
&lt;br /&gt;
Following procedure generates *.db and *.adl/*.alh files for High Voltage applications.&lt;br /&gt;
&lt;br /&gt;
  cd $APP/hvca/db/&lt;br /&gt;
&lt;br /&gt;
Create *.dat file with following format:&lt;br /&gt;
&lt;br /&gt;
  clonpc1:db&amp;gt; more caen.dat&lt;br /&gt;
  CAEN_1_00           02 1  1 01 01 03 00 -1200.0   1.5   1.3   121.5   486.0  2550.0 -2500.0&lt;br /&gt;
  CAEN_1_01           02 1  1 01 01 03 01 -1200.0   1.5   1.3   121.5   486.0  2550.0 -2500.0&lt;br /&gt;
  CAEN_1_02           02 1  1 01 01 03 02 -1200.0   1.5   1.3   121.5   486.0  2550.0 -2500.0&lt;br /&gt;
  CAEN_1_03           02 1  1 01 01 03 03 -1200.0   1.5   1.3   121.5   486.0  2550.0 -2500.0&lt;br /&gt;
  .....................................&lt;br /&gt;
&lt;br /&gt;
Columns have following meaning (NEED CHECK !):&lt;br /&gt;
&lt;br /&gt;
   1 - group name (channel name, will be used as part of EPICS channel access variable names)&lt;br /&gt;
   2 - group number&lt;br /&gt;
   3 - allow (?)&lt;br /&gt;
   4 - ioc number (that number goes to channel name, for example &#039;CAEN_&amp;lt;ioc number&amp;gt;_02&#039;)&lt;br /&gt;
   5 - mainframe address (for Lecroy by jumpers, for CAEN by IP, goes to channel name, for example &#039;CAEN_99_&amp;lt;mainframe address&amp;gt;)&lt;br /&gt;
   6 - slot/card number&lt;br /&gt;
   7 - submodule (?)&lt;br /&gt;
   8 - channel number&lt;br /&gt;
   9 - voltage (demand, V)&lt;br /&gt;
  10 - mvdz (measured voltage dead-zone, V)&lt;br /&gt;
  11 - mcdz (measuerd current dead-zone, uA?)&lt;br /&gt;
  12 - rump up speed, V/s&lt;br /&gt;
  13 - rump down speed, V/s&lt;br /&gt;
  14 - tc (trip current, uA?)&lt;br /&gt;
  15 - maximum voltage (max, V)&lt;br /&gt;
&lt;br /&gt;
Second input file is *.grp, for example caen.grp:&lt;br /&gt;
&lt;br /&gt;
  clonpc1:db&amp;gt; more caen.grp&lt;br /&gt;
  1  CAEN_7&lt;br /&gt;
  2  CAEN_3&lt;br /&gt;
  3  CAEN_7&lt;br /&gt;
  4  CAEN_8&lt;br /&gt;
  5  CAEN_10&lt;br /&gt;
&lt;br /&gt;
First column is group number and second one is group name. It will be first two columns on medm screen.&lt;br /&gt;
&lt;br /&gt;
Makefile must be manually adjusted for every new *.dat file. It is possible to combine several *.dat file in one - see inside Makefile.&lt;br /&gt;
&lt;br /&gt;
To generate all necessary file type &#039;make &amp;lt;filename without extension&amp;gt;&#039;, for example if file name is &#039;caen.dat&#039;, type:&lt;br /&gt;
&lt;br /&gt;
  make caen&lt;br /&gt;
&lt;br /&gt;
Following output fill shows up:&lt;br /&gt;
&lt;br /&gt;
  clonpc1:db&amp;gt; make caen&lt;br /&gt;
  ./dat2db.pl caen&lt;br /&gt;
  echo caen | /usr/local/clas/devel/R3.14.8.2/EPICS/app/hvca/bin/hv_adl&lt;br /&gt;
  Input name of hv data file (omit the extension &#039;.dat&#039;) :  &lt;br /&gt;
  WORKING ON GROUP #1&lt;br /&gt;
     Initializing variables to default values.&lt;br /&gt;
     Creating file: caen_CAEN_7_1.adl&lt;br /&gt;
     Initializing variables to default values.&lt;br /&gt;
     Creating file: caen_CAEN_7_param_1.adl&lt;br /&gt;
     Initializing variables to default values.&lt;br /&gt;
     Creating file: caen.adl&lt;br /&gt;
  ./dat2req.pl caen&lt;br /&gt;
  chmod +x caen*.csh&lt;br /&gt;
  test -d ../medm/adl || mkdir ../medm/adl&lt;br /&gt;
  test -d ../req || mkdir ../req&lt;br /&gt;
  mv caen*.adl ../medm/adl&lt;br /&gt;
  mv caen*.snap ../req&lt;br /&gt;
  mv caen*.csh ../medm/adl&lt;br /&gt;
  mv caen*.alarms ../medm/adl&lt;br /&gt;
  test -d ../medm/alh || mkdir ../medm/alh&lt;br /&gt;
  mv caen*.alhConfig* ../medm/alh&lt;br /&gt;
&lt;br /&gt;
Following files will be produced:&lt;br /&gt;
&lt;br /&gt;
  caen_01.db&lt;br /&gt;
  ../medm/adl/caen.adl&lt;br /&gt;
  .................adl&lt;br /&gt;
  ../medm/alh/caen_CAEN_7.alhConfig&lt;br /&gt;
  ../medm/alh/caen_mf_01_01.alhConfig_mf&lt;br /&gt;
&lt;br /&gt;
For NEW EPICS ONLY copy generated *.db files into final destination where it will be picked up by IOC startup script, for example:&lt;br /&gt;
&lt;br /&gt;
  cp caen_01.db $BASEB/src/CAEN_HV/IocShell/&lt;br /&gt;
  cp caen102_02.db $BASEB/src/CAEN_HV/IocShell/&lt;br /&gt;
&lt;br /&gt;
Create appropriate links to our medm files from standard place:&lt;br /&gt;
&lt;br /&gt;
  cd $APP/medm&lt;br /&gt;
  make&lt;br /&gt;
&lt;br /&gt;
Create appropriate links to our alh files from standard place:&lt;br /&gt;
&lt;br /&gt;
  cd $APP/alh&lt;br /&gt;
  make&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1775</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1775"/>
		<updated>2007-01-29T19:43:13Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
November 20, 2006&lt;br /&gt;
 Problem : Bad battery&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Called to APC  : 9-1-800-800-4272  then 4  then 3&lt;br /&gt;
 Operator       : David and Pole&lt;br /&gt;
 Case Number    : C1-121405343&lt;br /&gt;
 Internal Order : 1-121712992&lt;br /&gt;
 Solution       : APC will ship new battery&lt;br /&gt;
&lt;br /&gt;
November 22, 2006&lt;br /&gt;
 New battery arrived and installed&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
 Solution      : APC will ship new battery&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1774</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1774"/>
		<updated>2007-01-29T19:42:08Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
November 20, 2006&lt;br /&gt;
 Problem : Bad battery&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Called to APC  : 9-1-800-800-4272  then 4  then 3&lt;br /&gt;
 Operator       : David and Pole&lt;br /&gt;
 Case Number    : C1-121405343&lt;br /&gt;
 Internal Order : 1-121712992&lt;br /&gt;
 Solution       : APC will ship new battery&lt;br /&gt;
&lt;br /&gt;
November 22, 2006&lt;br /&gt;
 New battery arrived and installed&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1713</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1713"/>
		<updated>2007-01-26T18:09:45Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
November 20, 2006&lt;br /&gt;
 Problem : Bad battery&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Called to APC  : 9-1-800-800-4272  then 4  then 3&lt;br /&gt;
 Operator       : David and Pole&lt;br /&gt;
 Case Number    : C1-121405343&lt;br /&gt;
 Internal Order : 1-121712992&lt;br /&gt;
&lt;br /&gt;
November 22, 2006&lt;br /&gt;
 New battery arrived and installed&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1712</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1712"/>
		<updated>2007-01-26T18:05:24Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
November 20, 2006&lt;br /&gt;
 Problem : Bad battery&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Called to APC  : 9-1-800-800-4272  then 4  then 3&lt;br /&gt;
 Operator       : David and Pole&lt;br /&gt;
 Case Number    : C1-121405343&lt;br /&gt;
 Internal Order : 1-121712992&lt;br /&gt;
&lt;br /&gt;
November 22, 2006&lt;br /&gt;
 New battery arrived and installed&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1711</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1711"/>
		<updated>2007-01-26T18:04:16Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
November 20, 2006&lt;br /&gt;
 Problem : Bad battery&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Called to APC  : 9-1-800-800-4272  then 4  then 3&lt;br /&gt;
 Operator       : David and Pole&lt;br /&gt;
 Case Number    : C1-121405343&lt;br /&gt;
 Internal Order : 1-121712992&lt;br /&gt;
&lt;br /&gt;
November 22, 2006&lt;br /&gt;
 New battery arrived and installed&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1710</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1710"/>
		<updated>2007-01-26T18:00:48Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
November 20, 2006&lt;br /&gt;
 Problem : Bad battery&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Called to APC : 9-1-800-800-4272  then 4  then 3&lt;br /&gt;
 Operator      : David and Pole&lt;br /&gt;
 Internal Order: C1-121405343&lt;br /&gt;
&lt;br /&gt;
November 22, 2006&lt;br /&gt;
 New battery arrived and installed&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1709</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1709"/>
		<updated>2007-01-26T17:54:38Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation.&lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1708</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1708"/>
		<updated>2007-01-26T17:51:40Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
&lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure. &lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation. &lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement. &lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure.&lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement.&lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared.&lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared.&lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased.&lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared.&lt;br /&gt;
 11/20/2006 14:20:03 UPS: Passed internal self-test.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1707</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1707"/>
		<updated>2007-01-26T17:48:29Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
 11/20/2006 14:20:03 UPS: Passed internal self-test. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure. &lt;br /&gt;
 &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased.&lt;br /&gt;
 ...&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 ...&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1706</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1706"/>
		<updated>2007-01-26T17:46:39Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
&lt;br /&gt;
 11/22/2006 12:25:25 UPS: Number of batteries increased. &lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
 11/20/2006 14:20:03 UPS: Passed internal self-test. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:34:35 UPS: Internal battery temperature threshold violation cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:51 UPS: Number of batteries decreased. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:39 UPS: Battery failure cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:34 UPS: Bad battery condition cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:19 UPS: Batteries need immediate replacement. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:32:18 UPS: Battery failure. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:42 UPS: Battery failure cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:29 UPS: Bad battery condition cleared. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:23 UPS: Batteries need immediate replacement. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:22 UPS: Internal battery temperature threshold violation. &lt;br /&gt;
 &lt;br /&gt;
 11/20/2006 12:31:22 UPS: Battery failure. &lt;br /&gt;
 &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1705</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1705"/>
		<updated>2007-01-26T17:40:34Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note   : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1704</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1704"/>
		<updated>2007-01-26T17:39:25Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
January 22, 2007&lt;br /&gt;
 Note : New battery arrived and installed as R2 in Main Frame&lt;br /&gt;
 Model  # SYBT2&lt;br /&gt;
 Serial # QD0626150474&lt;br /&gt;
 SO     # 610051437&lt;br /&gt;
 Tested : Fri, Jun 30, 2006 00:18:28&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1703</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1703"/>
		<updated>2007-01-26T17:32:20Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1702</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1702"/>
		<updated>2007-01-26T17:31:11Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model   # SYBT2&lt;br /&gt;
 Serial  # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator      : Greg&lt;br /&gt;
 Case Number   : 1-179095349&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1701</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1701"/>
		<updated>2007-01-26T17:30:17Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
 Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
 Model # SYBT2&lt;br /&gt;
 Serial # ED0328001135&lt;br /&gt;
 Called to APC : 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
 Operator : Greg&lt;br /&gt;
 Case Number : 1-179095349&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1700</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1700"/>
		<updated>2007-01-26T17:28:32Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
January 18, 2007&lt;br /&gt;
&lt;br /&gt;
Problem : Bad battery R2 (Second right from top) in Main Frame&lt;br /&gt;
Model # SYBT2&lt;br /&gt;
Serial Number : ED0328001135&lt;br /&gt;
Called to APC: 9-1-800-800-4272 then 4 (for Techn.Support) then 3 (for Symmetra).&lt;br /&gt;
&lt;br /&gt;
Operator : Greg&lt;br /&gt;
Case Number : 1-179095349&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1699</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1699"/>
		<updated>2007-01-26T17:18:06Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;&#039;&#039;&#039;( Placed on the Right )&#039;&#039;&#039;&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1698</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1698"/>
		<updated>2007-01-26T17:17:28Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;Placed on the Right&lt;br /&gt;
 Type/Name     : Symmetra RM&lt;br /&gt;
 Model Number  : SYHF6KT&lt;br /&gt;
 Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1697</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1697"/>
		<updated>2007-01-26T16:53:11Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
Event Log of System Events :&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171.&lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased.&lt;br /&gt;
 01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1696</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1696"/>
		<updated>2007-01-26T16:51:33Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;Event Log of System Events :&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
12/04/2006 20:45:00 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:25 UPS: Batteries need immediate replacement. &lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:34 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
&lt;br /&gt;
01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:32:25 UPS: Number of batteries decreased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:34:32 UPS: Number of batteries increased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Battery failure cleared. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Number of batteries decreased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Bad battery condition cleared. &lt;br /&gt;
&lt;br /&gt;
01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:03:18 UPS: Number of batteries increased. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1695</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1695"/>
		<updated>2007-01-26T16:50:49Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;Event Log of System Events&lt;br /&gt;
&lt;br /&gt;
 12/04/2006 20:45:00 UPS: Passed internal self-test.&lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement.&lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test.&lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test.&lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased.&lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared.&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
12/04/2006 20:45:00 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:25 UPS: Batteries need immediate replacement. &lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:34 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
&lt;br /&gt;
01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:32:25 UPS: Number of batteries decreased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:34:32 UPS: Number of batteries increased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Battery failure cleared. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Number of batteries decreased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Bad battery condition cleared. &lt;br /&gt;
&lt;br /&gt;
01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:03:18 UPS: Number of batteries increased. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1694</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1694"/>
		<updated>2007-01-26T16:43:35Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;12/04/2006 20:45:00 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:24 UPS: Battery failure.&lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:25 UPS: Batteries need immediate replacement. &lt;br /&gt;
&lt;br /&gt;
01/16/2007 16:02:34 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
&lt;br /&gt;
01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:32:25 UPS: Number of batteries decreased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:34:32 UPS: Number of batteries increased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Battery failure cleared. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Number of batteries decreased. &lt;br /&gt;
&lt;br /&gt;
01/18/2007 11:35:01 UPS: Bad battery condition cleared. &lt;br /&gt;
&lt;br /&gt;
01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:03:18 UPS: Number of batteries increased. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:05:53 UPS: Passed internal self-test.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1693</id>
		<title>UPS CHB2</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_CHB2&amp;diff=1693"/>
		<updated>2007-01-26T16:34:39Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;12/04/2006 20:45:00 UPS: Passed internal self-test. &lt;br /&gt;
&lt;br /&gt;
01/22/2007 15:05:53 UPS: Passed internal self-test. &lt;br /&gt;
 &lt;br /&gt;
 01/22/2007 15:03:18 UPS: Number of batteries increased. &lt;br /&gt;
 &lt;br /&gt;
 01/20/2007 12:05:17 System: Detected an unauthorized user attempting to access the Web interface from 129.57.44.171. &lt;br /&gt;
 &lt;br /&gt;
 01/18/2007 11:35:01 UPS: Bad battery condition cleared. &lt;br /&gt;
 &lt;br /&gt;
 01/18/2007 11:35:01 UPS: Number of batteries decreased. &lt;br /&gt;
 &lt;br /&gt;
 01/18/2007 11:35:01 UPS: Battery failure cleared. &lt;br /&gt;
 &lt;br /&gt;
 01/18/2007 11:34:32 UPS: Number of batteries increased. &lt;br /&gt;
 &lt;br /&gt;
 01/18/2007 11:32:25 UPS: Number of batteries decreased. &lt;br /&gt;
 &lt;br /&gt;
 01/17/2007 14:19:06 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
 &lt;br /&gt;
 01/17/2007 14:18:09 UPS: Failed internal diagnostic self-test. &lt;br /&gt;
 &lt;br /&gt;
 01/16/2007 16:02:34 UPS: Passed internal self-test. &lt;br /&gt;
 &lt;br /&gt;
 01/16/2007 16:02:25 UPS: Batteries need immediate replacement. &lt;br /&gt;
 &lt;br /&gt;
 01/16/2007 16:02:24 UPS: Battery failure.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1692</id>
		<title>UPS Troubleshooting</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1692"/>
		<updated>2007-01-26T16:32:15Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;[[UPS CHB1]] and [[UPS CHB2]] are Symmetra RM multi-module and&lt;br /&gt;
multi-battery systems from APC Corporation.&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;[[UPS CHB1]]&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000736&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;[[UPS CHB2]]&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
We have contract with APC Corp. till &#039;&#039;&#039;2008&#039;&#039;&#039;&lt;br /&gt;
&lt;br /&gt;
Due to this contract we can contact them any time and ask them for help.&lt;br /&gt;
&lt;br /&gt;
  Technical Support Phone Number   :  800-555-2725&lt;br /&gt;
  or Direct Technical Support      :  800-800-4272 then 4 then 3&lt;br /&gt;
  or Web site for more Information :  http://apc.com/support/&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
In case of UPS is beeping or has blinking red light :&lt;br /&gt;
&lt;br /&gt;
* make a call to APC Technical Support&lt;br /&gt;
* be physically nearby to suspicious working UPS&lt;br /&gt;
* give them your name and our company name (Jefferson Laboratory)&lt;br /&gt;
* explain a problem&lt;br /&gt;
* ask them &#039;&#039;&#039;Operator Name&#039;&#039;&#039; and &#039;&#039;&#039;Case Number&#039;&#039;&#039;, write it down&lt;br /&gt;
* be ready to answer questions from Technical Support Operator&lt;br /&gt;
* be ready to dictate UPS’s Model Number and Serial Number &lt;br /&gt;
* be ready to follow Operator instructions to check UPS&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
At the end of check procedure broken module hopefully will be found.&lt;br /&gt;
APC normally send it to JLab within one-two days in a box with return tag.&lt;br /&gt;
After receiving and installation of new module, bad one should be returned to APC in delivered box, put return tag on the box. Box should be brought to our Shipping and Delivery in EEL building (Building 90). They will send it back to APC.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1691</id>
		<title>UPS Troubleshooting</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1691"/>
		<updated>2007-01-26T16:31:39Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;[[UPS CHB1]] and [[UPS CHB2]] are Symmetra RM multi-module and&lt;br /&gt;
multi-battery systems from APC Corporation.&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;[[UPS CHB1]]&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000736&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB2&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
We have contract with APC Corp. till &#039;&#039;&#039;2008&#039;&#039;&#039;&lt;br /&gt;
&lt;br /&gt;
Due to this contract we can contact them any time and ask them for help.&lt;br /&gt;
&lt;br /&gt;
  Technical Support Phone Number   :  800-555-2725&lt;br /&gt;
  or Direct Technical Support      :  800-800-4272 then 4 then 3&lt;br /&gt;
  or Web site for more Information :  http://apc.com/support/&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
In case of UPS is beeping or has blinking red light :&lt;br /&gt;
&lt;br /&gt;
* make a call to APC Technical Support&lt;br /&gt;
* be physically nearby to suspicious working UPS&lt;br /&gt;
* give them your name and our company name (Jefferson Laboratory)&lt;br /&gt;
* explain a problem&lt;br /&gt;
* ask them &#039;&#039;&#039;Operator Name&#039;&#039;&#039; and &#039;&#039;&#039;Case Number&#039;&#039;&#039;, write it down&lt;br /&gt;
* be ready to answer questions from Technical Support Operator&lt;br /&gt;
* be ready to dictate UPS’s Model Number and Serial Number &lt;br /&gt;
* be ready to follow Operator instructions to check UPS&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
At the end of check procedure broken module hopefully will be found.&lt;br /&gt;
APC normally send it to JLab within one-two days in a box with return tag.&lt;br /&gt;
After receiving and installation of new module, bad one should be returned to APC in delivered box, put return tag on the box. Box should be brought to our Shipping and Delivery in EEL building (Building 90). They will send it back to APC.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=CLON_Index&amp;diff=1687</id>
		<title>CLON Index</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=CLON_Index&amp;diff=1687"/>
		<updated>2007-01-26T16:18:05Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;[[Clon00]]&lt;br /&gt;
&lt;br /&gt;
[[Clon01]]&lt;br /&gt;
&lt;br /&gt;
[[Clon10]]&lt;br /&gt;
&lt;br /&gt;
[[Clondaq1]]&lt;br /&gt;
&lt;br /&gt;
[[Clonfs]]&lt;br /&gt;
&lt;br /&gt;
[[Clonfs2]]&lt;br /&gt;
&lt;br /&gt;
[[Clonpc2]]&lt;br /&gt;
&lt;br /&gt;
[[Clonweb]]&lt;br /&gt;
&lt;br /&gt;
[[clonhp]]&lt;br /&gt;
&lt;br /&gt;
[[clonhp2]]&lt;br /&gt;
&lt;br /&gt;
[[CycladesTS1000]]&lt;br /&gt;
&lt;br /&gt;
[[EtherLite32]]&lt;br /&gt;
&lt;br /&gt;
[[EPICS Base Installation]]&lt;br /&gt;
&lt;br /&gt;
[[EPICS: Software IOC]]&lt;br /&gt;
&lt;br /&gt;
[[EPICS: Software IOC for CAEN HV]]&lt;br /&gt;
&lt;br /&gt;
[[EPICS: generation of DBs and GUIs for HV]]&lt;br /&gt;
&lt;br /&gt;
[[EPICS: CVS usage examples]]&lt;br /&gt;
&lt;br /&gt;
[[EPICS: Gamma Profiler]]&lt;br /&gt;
&lt;br /&gt;
[[Slow Controls Time History]]&lt;br /&gt;
&lt;br /&gt;
[[Fiber Channel Switches]]&lt;br /&gt;
&lt;br /&gt;
[[Foundry BigIron 15000 Switch]]&lt;br /&gt;
&lt;br /&gt;
[[Foundry Switches]]&lt;br /&gt;
&lt;br /&gt;
[[Cisco Switches]]&lt;br /&gt;
&lt;br /&gt;
[[Linux Installation Procedure]]&lt;br /&gt;
&lt;br /&gt;
[[MRTG]]&lt;br /&gt;
&lt;br /&gt;
[[MySQL Installation]]&lt;br /&gt;
&lt;br /&gt;
[[MySQL Usage]]&lt;br /&gt;
&lt;br /&gt;
[[Nagios]]&lt;br /&gt;
&lt;br /&gt;
[[Nagios Plugins]]&lt;br /&gt;
&lt;br /&gt;
[[Nrpe]]&lt;br /&gt;
&lt;br /&gt;
[[OpenSSL]]&lt;br /&gt;
&lt;br /&gt;
[[Solaris Installation Procedure]]&lt;br /&gt;
&lt;br /&gt;
[[Troubleshooting printing]]&lt;br /&gt;
&lt;br /&gt;
[[UPS (Uninterruptible Power Supplies)]]&lt;br /&gt;
&lt;br /&gt;
[[UPS CHB1]]&lt;br /&gt;
&lt;br /&gt;
[[UPS CHB2]]&lt;br /&gt;
&lt;br /&gt;
[[UPS Troubleshooting]]&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1686</id>
		<title>UPS Troubleshooting</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1686"/>
		<updated>2007-01-26T15:42:57Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;UPS CHB1 and UPS CHB2 are Symmetra RM multi-module and&lt;br /&gt;
multi-battery systems from APC Corporation.&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB1&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000736&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB2&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
We have contract with APC Corp. till &#039;&#039;&#039;2008&#039;&#039;&#039;&lt;br /&gt;
&lt;br /&gt;
Due to this contract we can contact them any time and ask them for help.&lt;br /&gt;
&lt;br /&gt;
  Technical Support Phone Number   :  800-555-2725&lt;br /&gt;
  or Direct Technical Support      :  800-800-4272 then 4 then 3&lt;br /&gt;
  or Web site for more Information :  http://apc.com/support/&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
In case of UPS is beeping or has blinking red light :&lt;br /&gt;
&lt;br /&gt;
* make a call to APC Technical Support&lt;br /&gt;
* be physically nearby to suspicious working UPS&lt;br /&gt;
* give them your name and our company name (Jefferson Laboratory)&lt;br /&gt;
* explain a problem&lt;br /&gt;
* ask them &#039;&#039;&#039;Operator Name&#039;&#039;&#039; and &#039;&#039;&#039;Case Number&#039;&#039;&#039;, write it down&lt;br /&gt;
* be ready to answer questions from Technical Support Operator&lt;br /&gt;
* be ready to dictate UPS’s Model Number and Serial Number &lt;br /&gt;
* be ready to follow Operator instructions to check UPS&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
At the end of check procedure broken module hopefully will be found.&lt;br /&gt;
APC normally send it to JLab within one-two days in a box with return tag.&lt;br /&gt;
After receiving and installation of new module, bad one should be returned to APC in delivered box, put return tag on the box. Box should be brought to our Shipping and Delivery in EEL building (Building 90). They will send it back to APC.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1685</id>
		<title>UPS Troubleshooting</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1685"/>
		<updated>2007-01-26T15:42:29Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;UPS CHB1 and UPS CHB2 are Symmetra RM multi-module and&lt;br /&gt;
multi-battery systems from APC Corporation.&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB1&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000736&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB2&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
We have contract with APC Corp. till &#039;&#039;&#039;2008&#039;&#039;&#039;&lt;br /&gt;
&lt;br /&gt;
Due to this contract we can contact them any time and ask them for help.&lt;br /&gt;
&lt;br /&gt;
  Technical Support Phone Number   :  800-555-2725&lt;br /&gt;
  or Direct Technical Support      :  800-800-4272 -&amp;gt; 4 -&amp;gt; 3&lt;br /&gt;
  or Web site for more Information :  http://apc.com/support/&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
In case of UPS is beeping or has blinking red light :&lt;br /&gt;
&lt;br /&gt;
* make a call to APC Technical Support&lt;br /&gt;
* be physically nearby to suspicious working UPS&lt;br /&gt;
* give them your name and our company name (Jefferson Laboratory)&lt;br /&gt;
* explain a problem&lt;br /&gt;
* ask them &#039;&#039;&#039;Operator Name&#039;&#039;&#039; and &#039;&#039;&#039;Case Number&#039;&#039;&#039;, write it down&lt;br /&gt;
* be ready to answer questions from Technical Support Operator&lt;br /&gt;
* be ready to dictate UPS’s Model Number and Serial Number &lt;br /&gt;
* be ready to follow Operator instructions to check UPS&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
At the end of check procedure broken module hopefully will be found.&lt;br /&gt;
APC normally send it to JLab within one-two days in a box with return tag.&lt;br /&gt;
After receiving and installation of new module, bad one should be returned to APC in delivered box, put return tag on the box. Box should be brought to our Shipping and Delivery in EEL building (Building 90). They will send it back to APC.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1684</id>
		<title>UPS Troubleshooting</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1684"/>
		<updated>2007-01-26T15:36:44Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;UPS CHB1 and UPS CHB2 are Symmetra RM multi-module and&lt;br /&gt;
multi-battery systems from APC Corporation.&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB1&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000736&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB2&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
We have contract with APC Corp. till &#039;&#039;&#039;2008&#039;&#039;&#039;&lt;br /&gt;
&lt;br /&gt;
Due to this contract we can contact them any time and ask them for help.&lt;br /&gt;
&lt;br /&gt;
  Technical Support Phone Number   :  800-555-2725&lt;br /&gt;
  or Web site for more Information :  http://apc.com/support/&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
In case of UPS is beeping or has blinking red light :&lt;br /&gt;
&lt;br /&gt;
* make a call to APC Technical Support&lt;br /&gt;
* be physically nearby to suspicious working UPS&lt;br /&gt;
* give them your name and our company name (Jefferson Laboratory)&lt;br /&gt;
* explain a problem&lt;br /&gt;
* ask them &#039;&#039;&#039;Operator Name&#039;&#039;&#039; and &#039;&#039;&#039;Case Number&#039;&#039;&#039;, write it down&lt;br /&gt;
* be ready to answer questions from Technical Support Operator&lt;br /&gt;
* be ready to dictate UPS’s Model Number and Serial Number &lt;br /&gt;
* be ready to follow Operator instructions to check UPS&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
At the end of check procedure broken module hopefully will be found.&lt;br /&gt;
APC normally send it to JLab within one-two days in a box with return tag.&lt;br /&gt;
After receiving and installation of new module, bad one should be returned to APC in delivered box, put return tag on the box. Box should be brought to our Shipping and Delivery in EEL building (Building 90). They will send it back to APC.&lt;/div&gt;</summary>
		<author><name>Sergpozd</name></author>
	</entry>
	<entry>
		<id>https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1683</id>
		<title>UPS Troubleshooting</title>
		<link rel="alternate" type="text/html" href="https://clonwiki0.jlab.org/wiki/index.php?title=UPS_Troubleshooting&amp;diff=1683"/>
		<updated>2007-01-26T15:36:15Z</updated>

		<summary type="html">&lt;p&gt;Sergpozd: &lt;/p&gt;
&lt;hr /&gt;
&lt;div&gt;UPS CHB1 and UPS CHB2 are Symmetra RM multi-module and&lt;br /&gt;
multi-battery systems from APC Corporation.&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB1&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000736&lt;br /&gt;
&lt;br /&gt;
  &#039;&#039;&#039;UPS CHB2&#039;&#039;&#039;&lt;br /&gt;
  ========&lt;br /&gt;
  Type/Name     : Symmetra RM&lt;br /&gt;
  Model Number  : SYHF6KT&lt;br /&gt;
  Serial Number : ED0321000735&lt;br /&gt;
&lt;br /&gt;
We have contract with APC Corp. till &#039;&#039;&#039;2008&#039;&#039;&#039;&lt;br /&gt;
&lt;br /&gt;
Due to this contract we can contact them any time and ask them for help.&lt;br /&gt;
&lt;br /&gt;
  Technical Support Phone Number   :  800-555-2725&lt;br /&gt;
  or Web site for more Information :  http://apc.com/support/&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
In case of UPS is beeping or has blinking red light :&lt;br /&gt;
&lt;br /&gt;
* make a call to APC Technical Support&lt;br /&gt;
* be physically nearby to suspicious working UPS&lt;br /&gt;
* give them your name and our company name (Jefferson Laboratory)&lt;br /&gt;
* explain a problem&lt;br /&gt;
* ask them &#039;&#039;&#039;Operator name&#039;&#039;&#039; and &#039;&#039;&#039;Case Number&#039;&#039;&#039;, write it down&lt;br /&gt;
* be ready to answer questions from Technical Support Operator&lt;br /&gt;
* be ready to dictate UPS’s Model Number and Serial Number &lt;br /&gt;
* be ready to follow Operator instructions to check UPS&lt;br /&gt;
&lt;br /&gt;
&lt;br /&gt;
At the end of check procedure broken module hopefully will be found.&lt;br /&gt;
APC normally send it to JLab within one-two days in a box with return tag.&lt;br /&gt;
After receiving and installation of new module, bad one should be returned to APC in delivered box, put return tag on the box. Box should be brought to our Shipping and Delivery in EEL building (Building 90). They will send it back to APC.&lt;/div&gt;</summary>